Cross Connection Policy
No
customer served by the Sewanee Utility District will be permitted to
cross-connect the water service supplied by the District to any other water
supplier. No physical connections can be made by the customer to any other
distribution system or source other than that furnished by the District.
This
Policy consists of the following sections:
1.
Definitions
2.
Compliance with TCA
3.
Regulated
4.
Statement Required
5.
Applicability
6.
Inspections/Surveys
7.
Backflow Prevention Determination
8.
Approved Backflow Prevention Assemblies
9.
Backflow Prevention Assembly Installation Requirements
10.
Existing Backflow Prevention Assemblies
11.
Assembly Performance Evaluations and Testing
12.
Corrections of Violations
13.
Non-Potable Supplies
14.
Conflicting Provisions
15.
Penalties
16.
Responsibility for Water System
17.
Safety Standards-Duplicate Equipment in Parallel Suggested
18.
Effective Date
Section 1. The
following definitions and terms shall apply in the interpretation and
administration of this policy:
Air Gap: A physical separation between the free
flowing discharge end of a potable water supply line and an open or
non-pressurized receiving vessel.
Approved Air Gap: An air gap separation with a minimum distance
of at least twice the diameter of the supply line when measured vertically
above the overflow rim of the vessel, but in no case less than one (1) inch.
Approved: Any condition, method, device, procedure
accepted by the Tennessee Department of Environment and Conservation, Division
of Water Supply, and Water Provider.
Auxiliary Intake: Any piping connection or other device whereby
water may be secured from any sources other than from the public water system.
Auxiliary Water Supply: Any water supply on or available to the
premises other than water supplied by the public water system.
Backflow: The reversal of the
intended direction of flow of water or mixtures of water and other liquids,
gases, or other substances into the distribution pipes of a potable water
system from any source.
Backpressure:
A pressure in the downstream piping that is higher than the supply
pressure.
Backsiphonage:
Negative or Sub-atmospheric pressure in the supply piping.
Backflow Prevention Assembly: An approved assembly designed to prevent
backflow.
Bypass: Any system of piping or
other arrangement whereby water may be diverted around a backflow prevention
assembly, meter, or any other public water system controlled device.
Contamination: The introduction or admission of any
foreign substances that causes illness or death.
Contaminant:
Any substance introduced into the public water system that will cause
illness or death
Cross-Connection: Any physical arrangement whereby a water
supply is connected, directly or indirectly, with any other water supply
system, sewer, drain, conduit, pool, storage reservoir, plumbing fixture or
other device which contains, or may contain, contaminated water, sewage, or
other waste or liquid of unknown or unsafe quality which may be capable of
contaminating the public water supply as result of backflow caused by the
manipulation of valves, because of ineffective check valves or backpressure
valves or because of any other arrangement.
Cross-Connection Control
Coordinator/Manager: The person who is vested
with the authority and responsibility for the implementation of the
Cross-Connection Control Program and for the provision of this policy.
Customer:
Any natural or artificial person, business, industry, or governmental
entity that obtains water, by purchase or without charge, from the water
provider.
District: The
Sewanee Utility District of Franklin and Marion Counties
Double
Check Detector Assembly: A
specially designed assembly composed of line size approved double check valve
assembly, with a bypass containing a water meter and approved double check
valve assembly specifically designed for such application. The meter shall register accurately for very
low rates of flow up to 3 gallons per minute and shall show a registration for
all rates of flow. This assembly shall
only be used to protect against non-health hazards and is designed primarily
for use on fire sprinkler systems.
Double
Check Valve Assembly: An assembly of two
internally loaded check valves, either spring loaded or internally weighted,
installed as a unit between tightly closing resilient seated shutoff valves and
fitted with properly located resilient seated test cocks. This type of device shall only be used to
protect against non-health hazard pollutants.
Failed: The status of a backflow prevention assembly
determined by a performance evaluation based on the failure to meet all
minimums set forth by the approved testing procedure.
Fire
System Classifications Protection: The classes of fire
protection systems, as designated by the American Water Works Association “M14”
for cross-connection control purposes based on water supply source and the
arrangement of supplies, are as follows:
Class 1: Direct connection to the
public water main only; non pumps, tanks, or reservoirs; no physical connection
from other water supplies; no antifreeze or other additives of any kind; all
sprinkler drains discharging to the atmosphere, dry well or other safe outlets.
Class 2: Same as Class 1, except
booster pumps may be installed in connection from the street mains.
Class 3: Direct connection to
public water supply mains in addition to any one or more of the following: elevated storage tanks; fire pumps taking
suction from above ground covered reservoirs or tanks; and pressure tanks.
Class 4: Directly supplied from
public water supply mains, similar to Class 1 and Class 2, with and auxiliary
water supply dedicated to fire department use and available to premises, such
as an auxiliary supply located within 1700 feet of the pumper connection.
Class 5: Directly supplied from
public water supply mains and interconnection with auxiliary supplies such as
pumps taking suction from reservoirs exposed to contamination, or from rivers,
ponds, wells or industrial water systems; where antifreeze or other additives
are used.
Class 6: Combined industrial and
fire protection systems supplied from the public water mains only, with or
without gravity storage or pump suction tanks.
Hazard,
Degree of: A term derived from
evaluation of the potential risk to public health and the adverse effect of the
hazard upon the public water system.
Hazard,
Health: A cross-connection or
potential cross connection involving any substance that could, if introduced in
the public water supply, caused death, illness, and spread disease.
Hazard,
Plumbing: A cross-connection in a
customer’s potable water system plumbing that is not properly protected by an
approved air gap or backflow prevention assembly.
Hazard,
Non-health: A cross-connection or
potential cross-connection involving any substance that would not be a health
hazard but would constitute a nuisance or be aesthetically objectionable if
introduced into the public water supply.
Industrial
Fluid: Any fluid or solution that
may be chemically, biologically, or otherwise contaminated or polluted in a
form or concentration that could constitute a health, system, pollution, or
plumbing hazard if introduced into the public water supply. This shall include, but is not limited
to: polluted or contaminated water; all
type of process water or used water originating from the public water system
and that may have deteriorated in sanitary quality; chemicals; plating acids
and alkalis; circulating cooling water connected to an open cooling tower;
cooling towers that are chemically or biologically treated or stabilized with
toxic substance; contaminated natural water systems; oil, gases, glycerin,
paraffin, caustic , and acid solutions, and other liquids or gases used in
industrial processes, or for fire purposes.
Inspection: An on-site evaluation of an establishment to
determine if backflow prevention assemblies are needed by the customer to
protect the public water system from actual or potential cross connections.
Interconnection: Any system of piping or other arrangement
whereby a public water supply is connected directly with a sewer, drain, conduit,
or other device, which does, or may carry sewage or not.
Passed: The status of a backflow prevention assembly
determined by a performance evaluation in which the assembly meets all minimums
set forth by the approved testing procedure.
Performance
Evaluation: An evaluation of an
approved Double Check Valve Assembly or Reduced Pressure Principle Assembly
(including approved Detector Assemblies) using the latest approved testing
procedures in determining the status of the assembly.
Pollutant: A substance in the public water system that
would constitute a non-health hazard and would be aesthetically objectionable
if introduced into the public water supply.
Pollution: The presence of a pollutant or substance in
the public water system that degrades its quality so as to constitute a
non-health hazard.
Potable
Water: Water that is safe for
human consumption as prescribed by Tennessee Department of Environment and
Conservation, Division of Water Supply.
Public
Water Supply: An entity that furnishes
potable water for general use and which is recognized as the public water
supply by Tennessee Department of Environment and Conservation, Division of
Water Supply.
Pressure
Vacuum Breaker Assembly:
An assembly consisting of one or two independently operating spring
loaded check valve(s) and an independently operating spring loaded air inlet valve located on the discharge side of the check valve(s),
with tightly closing shutoff valve(s) on each side of the check valves and
properly located test cocks for testing valves.
This assembly is approved for internal use only and is not approved for
premise isolation by the State of Tennessee.
Public
Water System: A water system furnishing
water to the public for general use which is recognized as a public water
supply by the State of Tennessee.
Reduced
Pressure Principle Assembly: An assembly consisting of two independently
acting approved check valves together with hydraulically operating,
mechanically independent, pressure differential relief valve located between
the check valves and below the first check valve. These units shall be located between two
tightly closing resilient seated shutoff valves as an assembly and equipped
with properly located resilient seated test cocks.
Reduced
Pressure Principle Detector Assembly: A specially designed assembly composed of a
line-size approved reduced pressure principle backflow prevention assembly with
a bypass containing a water meter and approved reduced pressure principle
backflow prevention assembly specifically designed for such application. The meter shall register accurately for very
low flow rates of flows up to 3 gallons per minute and shall show registration
for all flow rates. This assembly shall
be used to protect against non-health and health hazards and used for internal
protection.
Service
Connection: The point of delivery to
the customer’s water system; the terminal end of a service connection from the
public water system where the water department loses jurisdiction and control
over the water. “Service Connection”
shall include connections to fire hydrants and all other temporary or emergency
water service connections made to the public water system.
State: The State of Tennessee, Tennessee Department of
Environment and Conservation, Division of Water Supply.
Survey: An evaluation of a premise by a water system
performed for the determination of actual or potential cross-connection hazards
and the appropriate backflow prevention needed.
Water
System: The water system operated,
whether located inside or outside, the corporate limits thereof, shall be
considered as made up of two (2) parts, the Utility System and the Customer
System.
A.
The utility system shall consist of the facilities for the
production, treatment, storage, and distribution of water, and shall include
all those facilities of the water system under the complete control of the
water department, up to the point where the customer’s system begins (i.e.
downstream of the water meter);
B.
The customer system shall include those parts of the facilities beyond
the termination of the water department distribution system that are utilized
in conveying water to the point of use.
Section 2.
The Sewanee
Utility District is to comply with Section 68-221-711 of the Tennessee Code
Annotated, as well as the Rules of Public Water Systems, legally adopted in
accordance with this Code, which pertain to cross-connections, auxiliary
intakes, bypasses, and interconnections, and establish an effective, ongoing
program to control these undesirable water uses.
Section 3.
- No
person shall cause a cross-connection, auxiliary intake, bypass, or
interconnection to be made, or allow one to exist for any purpose
whatsoever unless the construction and operation of same has been approved
by the Tennessee Department of Environment and Conservation and the
operation of such cross-connections, auxiliary intake, bypass, or
interconnection is at all times under the direct supervision of the Manager
of the Sewanee Utility District.
- No
water service connection to any premises shall be installed or maintained
by the Sewanee Utility District unless the water supply is protected as
required by this policy. Service of water to any premises shall be
discontinued by the District if a
backflow prevention assembly required by this policy is not properly
installed, tested, and/or maintained; or if it is found that a backflow
prevention assembly has been removed, bypassed, or if an unprotected
cross-connection exists on the premises.
Service shall not be restored until such conditions or defects are
correct.
- Prior
to execution any work order for a new customer, or for any change in
service to an existing customer, the Cross-Connection Control Manager/Coordinator
or designee shall make immediate determination if a backflow prevention
assembly is needed. If it is determined that a device is needed, the
customer will be notified in writing and water service shall not be
established or maintained until all necessary backflow prevention
assemblies are installed. A copy of this determination is to be filed with
the customer’s application for service.
- If,
in the judgment of the Cross-Connection Manager/Coordinator or designee,
an approved backflow prevention assembly is required at the water service
connection to a customer’s premises, or at any point(s) within the
premises, to protect the potable water supply, the manager shall compel
the installation, testing, and maintenance of the required backflow
prevention assembly(s) at the customer’s expense.
- An
approved backflow prevention assembly shall be installed on each water
service line to a customer’s premises at or near the property line or
immediately inside the building being served; but in all cases before the
first branch line leading off the service line.
- For
new installations, the manager or his designee shall inspect the site
and/or review plans in order to assess the degree of hazard and to
determine the type of backflow prevention assembly, if any, that will be
required, and to notify the owners in writing of the required assembly and
installation criteria. All required
assemblies shall be installed and operational prior to initiation of water
service.
- For
all existing premises, personnel from the District shall conduct
inspections and evaluations, and shall require correction of violations in
accordance with the provisions of this policy.
- For
existing installations, the Cross-Connection Manager/Coordinator may cause
water service to be discontinued until such time as the customer complies
with all requirements of state law and this policy.
- For
new commercial or industrial construction or renovation of a commercial or
industrial property, the Cross-Connection Coordinator/Manager or inspector
shall inspect the site and review plans in order to determine the type(s)
of backflow prevention assembly and notify the owner(s) in writing the
type of required assembly(s). Such
assembly(s) shall be tested within 30 days upon connection to water
system.
- The
customer shall install approved assembly(s) at their expense.
Failure, refusal, or inability on the part of the customer to
install, and maintain such an assembly shall be cause for discontinuance
of, or refusal of, water service to the premises until such requirements
are satisfactorily met.
- No
installation, alteration or change(s) shall be made to any backflow
prevention assembly connected to the public water system without first
securing permission from the Cross-Connection Manager/Coordinator.
- All
backflow prevention assemblies will inspected after installation for
compliance with all requirements of this policy. Failure to meet all installation and
testing requirements shall be cause for discontinuance of, or refusal of,
water service to the premises until such requirements are satisfactorily
met.
- It
shall be unlawful to install or allow any unprotected takeoffs from the
water service line ahead of any meter or backflow prevention assembly
located directly after the service connection to a customer’s water
system.
Section 4.
That
any person whose premises are supplied with water from the Sewanee Utility
District, and who also has on the same premises a separate source of water
and/or water stored in an uncovered or unsanitary storage reservoir from which
the water stored therein is circulated through a piping system, shall file with
the District a statement of the nonexistence of unapproved or unauthorized
cross-connections, auxiliary intakes, bypasses, or interconnection. Such statement shall also contain an
agreement that no cross-connection, auxiliary intake, bypass, or interconnection
will be permitted upon the premises.
Section 5.
The
requirements contained herein shall apply to all customers of the Sewanee
Utility District, and is hereby made a condition required to be met before
water service is provided to any customer.
This policy shall be strictly enforced since it is essential for the
protection of the public water supply against contamination and pollution.
Section 6.
- The
Cross-Connection Manager/Coordinator shall inspect all properties served
by the District where cross-connections with the public water supply are
deemed possible. The frequency of
inspections and re-inspections based on potential health hazards involved
shall be established by the Cross-Connection Manager/Coordinator in
accordance with guidelines acceptable to the Division of Water
Supply.
- The
Cross-Connection Manager/Coordinator or designee shall have the right to
enter at any reasonable time any property served by a connection to the Sewanee
Utility District for the purpose of inspecting the piping system therein
for cross-connections, auxiliary intakes, bypasses, or
interconnections. On request, the
owner, lessee, or occupant or any property so served shall furnish any
pertinent information regarding the piping system on the property. The refusal of such information or
refusal of access, when requested, shall be deemed as evidence of the
presence of connections.
- When
cross-connections, other structural or sanitary hazards, or any violation
of this becomes known, the Cross-Connection Manager/Coordinator or
designee may deny or discontinue service to the premises by providing for
a physical break in the service line until the customer has corrected the
conditions(s) in conformance with this policy.
Section
7.
An approved backflow prevention assembly shall be installed on
each service line to a customer’s premises within 10 feet of the water meter and
in all cases, before the first branch line leading off the service line, if it
is impractical or easily altered to provide an effective air gap separation,
when any of the following conditions exist:
- Premises
where industrial fluids, sewage, or any other non-potable substances are
handled in such a manner as to create actual or potential health hazard to
the water system.
- Premises
having internal cross connections that cannot be permanently corrected and
controlled, intricate plumbing and piping arrangements, or where entry to
all portions of the premises is not readily accessible for inspection
purposes making it impractical or impossible to ascertain whether or not
cross-connections exist.
- Premises
having auxiliary water supply, including but not limited to a well,
cistern, spring, pond, river , or creek that is not, or may not be, of
safe bacteriological or chemical quality and that is not acceptable as an
additional source by the Cross-Connection Control Manager/Coordinator or
designee.
- The
plumbing from a private well or other water supply entering the building
served by the public water supply, or is connected, directly or
indirectly, to the public water supply.
- The
owner or occupant of the premises cannot, or is not willing to demonstrate
that the water use and protective features of the plumbing are such that
frequent alterations are made to the plumbing.
- The
nature and mode of operation within the premises is such that frequent
alterations are made to the plumbing.
- The
nature of the premises is such that the use of the structure may change to
a use wherein backflow prevention is required.
- There
is likelihood that protective measures may be subverted, altered, or
disconnected.
- Any
premises having service and fire flow connections, most commercial and
educational buildings, construction sites, all industrial and medical
facilities, lawn irrigation systems, public or private swimming pools,
private fire hydrant connections used by any fire department in combating
fires, photographic laboratories, standing ponds or other bodies of water,
auxiliary water supplies, and
wastewater treatment plants.
- Any
premises having fountains, water softeners or other point of use treatment
systems hot tubs or spas, or other type(s) of water using equipment.
- Premises
otherwise determined by the Cross-Connection Control Manager/Coordinator
or designee to create an actual or potential hazard to the public water
system.
- In
the case of any premises where there is any material dangerous to health
that is handled in such a fashion as may create an actual or potential
health hazard to public water system, the public water system shall be
protected a reduced pressure principle backflow prevention assembly. The following premises, where such
conditions may exist, include but are not limited to: sewage treatment plants, sewage pumping
stations, chemical manufacturing plants, hospitals, mortuaries, funeral
homes, and metal plating operations.
- In
the case of any premises where, because of security requirements or other
prohibitions or restriction it is impossible or impractical to make a
complete cross-connection survey, the public water system shall be
protected against backflow from the premises by a reduced pressure
principle assembly on each service line to the premises immediately after
the customer’s meter(s).
- A
backflow prevention assembly shall be installed on each fire service line immediately
after the connection point with the District’s main line, (or at the
nearest practical point to that connection, if approved by the Manager of
the District) , but in all cases, before the first branch line leading off
the service line wherever any of the following conditions exist:
1. Class 1,2, and 3 fire protection systems shall require at minimum
a double check valve assembly; however, a
reduced pressure principle shall be required if :
a. Underground fire sprinkler pipelines are parallel to and within
(10’) feet horizontally of pipelines carrying waste water or significantly
toxic wastes; or
b. Premises having unusually complex piping systems;
c. The pumpers connecting to the system have corrosion inhibitors or
other chemical added to the tanks of the fire trucks;
d. The piping system(s) has corrosion inhibitors or other chemical
added to prevent freezing;
e. An auxiliary water supply exists with 1,700 feet of any likely
pumper connection.
2. Class 4, Class 5, Class 6
fire protection systems shall require an air gap, or a reduced pressure
principle assembly as determined by the
Cross –Connection Control Manager/Coordinator
or designee.
3. Where a fire sprinkler system is installed on the premises, a
minimum of a double check valve assembly shall be required.
4. Where a fire sprinkler system uses chemicals, such as liquid foam,
to enhance fire suppression a reduced pressure principle detector assembly
shall be required.
The Cross-Connection Control Manager/Coordinator may require
internal or additional backflow prevention devices where it is deemed necessary
to protect potable water supplies within the premises.
- Double
Check Valve Assemblies (and Detectors) may only be used for Class 1-3 fire protection systems.
- In
the case of any premises where there are uncontrolled cross-connections,
either actual or potential, the public water system shall be protected by
a reduced pressure principle assembly on each service line to the
premises.
- In
the case of any premises where toxic substances are present that could
pose an undue health hazard, the Cross-Connection Control
Manager/Coordinator or designee may require an air gap separation or
reduced pressure principle assembly at the service connection to protect
the public water system. In making
this determination, the Cross-Connection Control Manager/Coordinator or his
designee shall consider the degree of hazard.
Section 8.
- All
backflow prevention assemblies shall be fully approved and listed as
acceptable by the State of Tennessee
as to manufacture, model, size, application, orientation, and
alterations. The device must have a
status of Passed determined by performance evaluations to suffice as an
approved backflow prevention assembly.
The method of installation of backflow prevention devices shall
comply with installation criteria set forth by the State of Tennessee. Installation shall be at the sole
expense of the owner of the owner or occupant of the premises.
- The type of
protective assembly required by this Policy shall depend on the degree of
hazard that exists. Reduced
Pressure Principle Assemblies may be used for health hazards and
non-health hazards. Double Check
Valve Assemblies may only
be used for non-health hazards and is limited to Class 1-3 fire systems
only.
- Pressure vacuum breakers,
spill-resistant vacuum breakers, and atmospheric vacuum breaker are not
allowed for premise isolation and will not satisfy the requirements of
this Policy for adequate backflow prevention due in part to the inability
to protect against backpressure.
Section
9.
Minimum acceptable criteria for installation of backflow
prevention assemblies shall include the following:
- All
backflow prevention assemblies shall be installed at minimum in the
approved orientation as indicated by the latest Approved List.
- Installation
of assemblies shall be performed by person granted authority by the District. All backflow prevention assemblies
installed fire protection systems must be performed by persons possessing
a fire sprinkler contractor license.
Evidence of current certifications/license must be on file with the
Cross-Connection Control Manager/Coordinator before any installation or
testing of the devices can be performed.
- All
assemblies shall be installed in accordance with the manufacturer
installation instructions and by the State of Tennessee installation
guide, from the State Manual or policies on cross-connection control,
unless such instructions are in conflict with this policy, in which case
the policy shall control, and shall possess all test cocks and fittings
required for testing the assembly.
All test cocks will be fitted with adapters and all fittings shall
permit direct connection to test kits used by the District.
- The
entire assembly including test cocks and valves shall be easily accessible
for testing and repair and shall meet all confined space requirements of
OSHA/TOSHA.
- Reduced
Pressure Backflow Prevention Assemblies shall be located so that the
relief valve discharge port is a minimum of twelve (12) inches, plus
nominal diameter of the supply line, above the floor surface. The maximum height above the floor surface
shall not exceed sixty (60) inches.
- Clearance
of devices from wall surfaces or other obstructions shall be a minimum of
six (6) inches; or if a person must enter the enclosure for repair or
testing, the minimum distance shall be twenty-four inches.
- Devices
shall be protected from freezing, vandalism, mechanical abuse, and from
any corrosive, sticky, greasy, abrasive, or other damaging substance.
- Devices
shall be positioned where discharge from a relief port will not create
undesirable conditions. An approved
air gap shall separate the relief port from any drainage system. Such air-gap shall not be altered
without the specific approval of the District.
- Devices
shall be located in an area free from submergence or flood potential.
- All
devices shall be adequately supported to prevent sagging.
- An
approved strainer, fitted with a test cock, shall be installed immediately
upstream of all backflow prevention assemblies or shut-off valve, except
on fire lines, using only non-corrosive fittings (e.g. brass or bronze) in
the device assembly.
- Gravity
drainage is required on all installations.
Below ground installations shall not be permitted for Reduced
Pressure Principle Assemblies (detectors).
- Fire
hydrants drains shall not be connected to the sanitary sewer, and fire
hydrants shall not be installed in such manner that backsiphonage or
backflow through the drain may occur.
- Where
jockey (low volume-high pressure) pumps are utilized to maintain elevated
pressure, as in fire protection system, the discharge of the pump shall be
on the downstream side of any check valve or backflow prevention
assembly. Where the supply for the
jockey pump is taken from the upstream supply side of the check valve or
backflow prevention assembly, a backflow prevention assembly of the same
type(s) required on the main line shall be installed on the supply line.
- Fixed
position, high volume fire pumps shall be equipped with suction limiting
control to modulate the pump if the residual line pressure reaches 20
psi. If line pressure drops below
20 psi, the pump will shut off to protect the distribution system. This shut off system must be tested
annually for proper operation and report of the test must be sent to the
office of Cross-Connection Control.
- All
new assemblies installed must be on the Approved Assemblies List
maintained by the Division of Water Supply and existing assemblies must
have status of approved.
Section 10.
- All
presently installed backflow prevention assemblies which were previously
acceptable to the State of Tennessee that complies with installation,
testing, and maintenance requirements of this policy and in the sole
discretion of the Cross-Connection Control Manager/Coordinator or designee
adequately protect the public water system from backflow and that were
approved assemblies for the purpose described herein at the time of
installation may be retained in service.
- Location
or space requirements shall not be cause for re-location or replacement of
any backflow prevention assembly that is presently installed in a vertical
run of pipe shall be replaced, reinstalled, in an approved manner in a
horizontal run of pipe.
- Wherever
an existing assembly is moved from the present location, or when the
inspector finds that the conditions of the assembly constitutes a health
hazard, the unit shall be replaced by the backflow prevention assembly
meeting the requirements of this policy.
Section 11.
- All
assemblies used to protect the public water system must be tested every 12
months.
- All
performance evaluations, tests, and repairs shall be at the expense of the
customer and shall be performed by backflow prevention assembly testers
that satisfy all requirements of this ordinance/policy.
- All
assemblies must be deemed Passed for
each initial and subsequent annual performance evaluations to qualify as an
approved backflow prevention assembly.
- All
assemblies will be tested by backflow prevention assembly tester with a
valid (see definition) Certificate of Competency in Testing and Evaluation
Backflow Prevention Assemblies issued by the State of Tennessee.
- All
performance evaluations must be performed with an annually certified test
kit.
- Certifications
for test kits are valid for one year after certification is
performed. If the test kit is not
recertified after one year, it is deemed expired.
- Test
kits must be certified annually and the backflow prevention assembly
tester must show proof of certification from manufacturer-approved
entities. No performance
evaluations will be accepted from a backflow prevention assembly tester with
an expired test kit certification.
- Proof
of annual test kit certification and a Certificate of Competency for each
tester must be provided to the District before any device is tested.
- Backflow
Prevention Assembly Testers must test and evaluate according to the latest
Division of Water Supply’s approved procedures for Reduced Pressure
Principle Assembly and the Double Check Valve Assembly.
- If any test does not meet the minimum
requirements set forth in the approved testing procedure, the assembly is
deemed Failed and does not
suffice as an approved backflow prevention device. If conditions around the assembly do not
allow the assembly to be tested, the assembly fails the assembly
performance evaluation and is marked Failed
on test report. (Examples would include assembly is submerged, test cocks
missing or plugged, relief valve continually discharging).
- Backflow
Prevention Assemblies are deemed Passed
if all parts of the performance evaluation meet the minimum requirements
in the approved testing procedure.
- Each
location requiring an assembly will have a documented backflow prevention
assembly, if the assembly at the address cannot be identified or is not
the same, the District will be notified and a determination of which is
assembly is used for protection of the water system. (All areas that need protection will be
listed by address and location along with the serial no. of device)
- Test
reports must be completely and accurately documented and the appropriate
evaluation (Passed or Failed) determined from testing
procedure. Any test report that is
not recorded completely in the sections pertinent to the results of the
performance evaluation tests will not be accepted by the District.
- All
performance evaluations on file will be recorded on a Sewanee Utility
District and/or State approved test report.
- Assemblies
must be tested when installed and after every repair. Backflow prevention assemblies on lawn
irrigation systems must be tested when assemblies are placed in service
after winterization (To prevent testing just prior to winterization). If lawn irrigation backflow assemblies
are taken removed to winterize the system, upon startup of the system, the
assemblies must be retested.
- Failure
to maintain a backflow prevention assembly that is deemed Passed shall be grounds for
discontinuance of water service.
The removal, bypassing, or altering of a protective device or
installation, without the approval of the Cross-Connection Control
Manager/Coordinator or designee, thereof so as to render a device ineffective
shall constitute grounds for discontinuance of water service. Water service to such premises shall
not be restored until the customer has corrected or eliminated such
conditions or defects to the satisfaction this ordinance/policy and the
Cross-Connection Control Manager/Coordinator or designee.
- The
District shall require the occupant of the premises to keep the backflow
prevention assembly working properly and a status of Passed. Repairs shall
be made by qualified personnel acceptable to the District within the time
limits set forth by this policy.
Expense of such repairs shall be borne by the owner or occupant of
the premises. The failure to maintain a backflow prevention assembly in
proper working order and a status of Passed shall be grounds for
discontinuance of water service.
- The
backflow prevention assembly must be tested after every repair and have a
status of Passed to be in compliance with this policy.
- Cross-Connection
Control Manager/Coordinator or designee shall have the right to inspect
and test any assemblies whenever it is deemed necessary. Water service shall not be disrupted to
the assembly without the knowledge of the occupant of the premises.
- Any
backflow prevention assembly tester found by the water system to be
negligent in performing testing procedures or falsifying documentation in
regards to a backflow prevention assembly will not be allowed continued
approval to submit test reports.
The District may allow the backflow prevention assembly tester to
perform testing at a later date, at the discretion of the Cross-Connection
Control Manager/Coordinator or designee.
- Backflow
prevention assembly testers must have approval from the Sewanee Utility
District before any test reports are accepted. The District will issue a copy of the
latest approved policy from the District and require the signature of the
tester acknowledging requirements and responsibilities before allowance of
submittal of test reports.
- Original
records of evaluations and repairs shall be supplied to the Cross-Connection
Control Manager/Coordinator or designee for retention.
- Any
assembly not tested within a 12 month period will be deemed not approved
and have a status of Failed.
The customer will be sent notification that the assembly is not in
compliance with this policy.
Section
12.
- Any
customer having cross-connections, auxiliary intakes, bypasses, or
interconnection(s) in violation of this ordinance shall, after a thorough
investigation of existing conditions and an appraisal of the time
required, complete the work within the time designated by the
Cross-Connection Control Manager/Coordinator or designee, but in no case
shall the time for correction exceed ninety (90) days.
- Failure
to comply with any order of the Cross-Connection Control
Manager/Coordinator or designee within the time set out therein shall
result in the termination of water service.
- Where
cross-connections, auxiliary intakes, bypasses, or interconnections are
found to constitute an extreme hazard of immediate concern of
contaminating the public water supply such as proximity to toxic waste or
an extreme biological hazard, the Cross-Connection Control
Manager/Coordinator or designee shall require immediate corrective action
be taken to eliminate the threat.
Expeditious steps shall be taken to disconnect the public water
system from the customer’s piping systems unless the extreme hazard is
correctly immediately.
- Upon
written request by the customer, the Cross-Connection Control
Manager/Coordinator or designee shall provide a hearing regarding any
order of termination or refusal of water service; provided however, that
when an order is issued pursuant to subsection (C) of this section, such
hearing may be held after such termination or refusal, but not later that
five (5) working days after receipt of the request. Any customer aggrieved by such an order
may appear in person, or by legal counsel, and show cause
why an order to terminate water service, or to refuse water service,
should be rescinded.
- In
the case of failed or nonexistent protection on an extreme high hazard and
high hazard cross connection threat that does not qualify as a threat of
immediate concern under Section C (above), the Cross-Connection Control
Manager/Coordinator or designee will notify the customer of the length of
time allowed for the correction of said violations. The length of time
allowed will be dependent upon the severity of the hazard, but in no case
will more than 30 days be granted to correct the violation.
- Failure
to correct conditions threatening the safety of the public water system as
prohibited by this ordinance or Tennessee Code Annotated 68-221-711 within
the time limits set by the Cross-Connection Control Manager/Coordinator or
designee or this ordinance/policy, shall be cause for denial or
termination of water service. If
proper protection is not provided after times set forth in this policy,
the Cross-Connection Control Manager/Coordinator or designee shall give
the customer written notification that water service is to be
discontinued, and thereafter physically separate the public water system
from the customer’s system in such a manner that the two systems cannot be
connected by an unauthorized person.
- In the event that a backflow prevention
assembly is deemed Failed (Initial or Annual Performance Evaluation),
failure to install backflow prevention assemblies as requested by the District,
or there are deficiencies in the installation from failure to conform to
the installation criteria specified in this ordinance, or from
deterioration, then the Cross-Connection Control Manager/Coordinator or
designee shall issue a written notice of failure or deficiency within 14
days. The time limit to correct the
deficiencies or repair the assembly is dependent on risk of contamination,
but in no case will it be greater than 90 days.
Section
13.
- Any
water outlet connected to auxiliary water sources, industrial fluid
systems, or other piping containing non-potable liquids or gases, which
could be used for potable or domestic purposes, shall be labeled in a
conspicuous manner as:
WATER UNSAFE FOR DRINKING
- The
minimum acceptable sign shall have black letters at least one inch (1”)
high on red background.
- Color
coding of piping in accordance with Occupational Safety and Health Act
guidelines may be required in locations where, in the judgment of the
inspector, such color coding is necessary to identify and protect the
potable water supply.
Section
14.
If any provision of this ordinance/policy is found to conflict
with any provision of any other ordinance/policy, then the provision of this
ordinance shall control. That should any
part or parts of this ordinance be declared invalid for any reason, no other
part, or parts, of this ordinance shall be affected thereby.
Section
15.
Any person responsible for a violation of this policy may be
subject to a penalty of not less than $50 or more than $500. Each day a violation occurs shall constitute
a separate offense. In addition to the
foregoing fines and penalties, the Cross-Connection Control Manager/Coordinator
or designee shall discontinue the public water service at any premises upon
connection and service shall not be restored until such cross-connection,
auxiliary intake, bypass, or interconnection has been discontinued. Additional
fees associated with restoring service and other services may apply.
Section 16.
A. Notwithstanding any provisions of a plumbing
code adopted by units of local government having jurisdiction, the
Cross-Connection Control Manager/Coordinator or designee shall be responsible
for protecting the water system from contamination or pollution due to
implementation and enforcement of this policy.
Such authority shall extend beyond service connection to whatever extent
is necessary to meet the requirements of this policy.
B. The
authority to terminate water service for violation of any provision of this
policy shall rest solely with the Cross-Connection Control Coordinator/Manager,
the District Manager, or their designee, and they shall have authority to take
action to protect public health and safety.
C. This
section shall not be construed to prevent other officers or employees of the Sewanee
Utility District from terminating water service for failure to pay for water
service, or for violation any other provision of District policy.
Section
17.
Where the use of water is critical to the continuation of normal
operations or protection of life, property, or equipment, it is recommended
that duplicate units shall be provided to avoid the necessity of discontinuing
water service to test or repair a backflow prevention assembly. Until such time as a parallel unit has been
installed where the continuance of service is critical, the Cross-Connection
Control Manager/Coordinator or designee shall notify the occupant of the premises,
in writing, of plans to interrupt water service and arrange for a mutually
acceptable time to test the assembly.
Section
18.
This policy shall take effect immediately.
Approved this _________ day of ____________, 2_______
_____________________________
Ken
Smith, Secretary